Description
The Dutypoint Vortech Compact pumping station is a fully assembled package, ready for immediate installation. For detailed installation guidelines and to schedule professional Dutypoint commissioning, please contact us
- Large Domestic Properties
- Multi-property housing developments
- Medium size retail and commercial
Important Note: Dutypoint Vortech polyethylene underground chambers are not suitable for installations where groundwater levels may exceed 2 meters above the chamber base. It is essential to follow the provided installation instructions.
Chamber Specifcation:
| Chamber Model | Grand 25 | Grand 30 | Grand 40 |
| Internal Diameter (m) | 1.5 | 1.8 | 1.8 |
| Depth (m) | 2.5 | 3.2 | 4.2 |
| Nominal Capacity (L) | 3000 | 6500 | 9000 |
| Access Opening | 800 x 1000 | 800 x 1000 | 800 x 1000 |
Pump Specification:
| Pump Model | V28 | G10 | V81 |
| Application | Foul or Grey Water | Foul Water | Foul or Grey water |
| Power Supply | 230v Single Phase | 230v Single Phase | 230v Single Phase |
| Kw Rating | 0.75 kw | 1 kw | 1.5 kw |
| Full Load Current | 4.2 amps | 6.4 amps | 10 amps |
| Impeller Type | Vortex | Grinder | Vortex |
| Solids Passage | 50mm | N/A | 76mm |
| Max flow | 6 l/s | 2.2 l/s | 12 l/s |
| Max Head | 10m | 20m | 8m |
| Final Discharge Connection | 2″ BSP Male | 2″ BSP Male | 3″ BSP Male |